A-4.2
Door interface
Door A-12 uses an electric strike on SC-410 Output 2. The project design records the lock as fail-secure. Normal access operation is distinct from the fire-release function.
Project Specification · REVISION A
Fictional / anonymised ENGGEN 720 demonstration source. SiteAssist reads the stored sections below through controlled read-only tools.
A-4.2
Door A-12 uses an electric strike on SC-410 Output 2. The project design records the lock as fail-secure. Normal access operation is distinct from the fire-release function.
A-5.1
The fire alarm interface is connected to supervised input FAI-1. Door release on fire alarm is a life-safety function and requires a witnessed commissioning test against the approved test script.
A-7.3
RS-485 reader devices are arranged as a daisy chain. The final device requires 120 ohm end-of-line termination; star wiring is not permitted.