4.1
Door output mode
Firmware 4.3 introduces Lock Type: Fail-safe or Fail-secure. Select the type that matches the approved door hardware schedule. Do not use the legacy Invert Output workaround from firmware 4.2.
Installation Manual · REVISION C
Fictional / anonymised ENGGEN 720 demonstration source. SiteAssist reads the stored sections below through controlled read-only tools.
4.1
Firmware 4.3 introduces Lock Type: Fail-safe or Fail-secure. Select the type that matches the approved door hardware schedule. Do not use the legacy Invert Output workaround from firmware 4.2.
4.7
The fire interface must be proven by a witnessed functional test. Local Door Control overrides must not prevent the required safe-state transition.
6.3
Use daisy-chain topology and one 120 ohm termination at the physical end of the reader bus.