Installation Manual · REVISION C

SC-410 Installation Manual — Rev C project copy

Fictional / anonymised ENGGEN 720 demonstration source. SiteAssist reads the stored sections below through controlled read-only tools.

Advisory
Document typeInstallation Manual
RevisionC
System version scope4.3 → 4.3
Published18 Jul 2025
Evidence groupBEACON
Source scopeProject History
Original formatPDF
Eligible source. The agent may retrieve this document only when product/version scope and relevance checks also pass.

Stored source sections

3 sections

4.1

Door output mode

Source section

Firmware 4.3 introduces Lock Type: Fail-safe or Fail-secure. Select the type that matches the approved door hardware schedule. Do not use the legacy Invert Output workaround from firmware 4.2.

4.7

Fire interface

Source section

The fire interface must be proven by a witnessed functional test. Local Door Control overrides must not prevent the required safe-state transition.

6.3

Reader bus

Source section

Use daisy-chain topology and one 120 ohm termination at the physical end of the reader bus.