OBS-B-011.1
Observed symptom
Door B-04 showed Access Granted but lock behaviour was reversed during commissioning.
Observation Sheet · REVISION 1
Fictional / anonymised ENGGEN 720 demonstration source. SiteAssist reads the stored sections below through controlled read-only tools.
OBS-B-011.1
Door B-04 showed Access Granted but lock behaviour was reversed during commissioning.
OBS-B-011.2
The configuration had copied Atlas firmware 4.2 Invert Output logic into a firmware 4.3 controller.
OBS-B-011.3
The legacy inversion was removed and Lock Type was set to Fail-safe in accordance with the Beacon door schedule and Rev C manual. Retest passed.