4.2
Lock Type configuration
For firmware 4.3 and later, configure each door output as Fail-safe or Fail-secure to match the approved hardware schedule. Legacy Invert Output logic is not the commissioning method for these versions.
Installation Manual · REVISION D
Fictional / anonymised ENGGEN 720 demonstration source. SiteAssist reads the stored sections below through controlled read-only tools.
4.2
For firmware 4.3 and later, configure each door output as Fail-safe or Fail-secure to match the approved hardware schedule. Legacy Invert Output logic is not the commissioning method for these versions.
6.3
Install one 120 ohm termination at the physical end of each reader bus. Missing or duplicated termination can cause intermittent communication errors.
9.1
Life-safety interfaces require the project-approved witnessed test and cannot be accepted from normal access-control results.