TB-031.1
Symptom
Reader devices may briefly drop offline while the controller remains reachable. CRC errors may accumulate slowly over several hours.
Manufacturer Bulletin · REVISION A
Fictional / anonymised ENGGEN 720 demonstration source. SiteAssist reads the stored sections below through controlled read-only tools.
1 approved answer depend on this source.
KB-0001 · SME resolution: reader bus intermittent evidence · Approved
TB-031.1
Reader devices may briefly drop offline while the controller remains reachable. CRC errors may accumulate slowly over several hours.
TB-031.2
Record reader-bus CRC counters, topology, end-of-line termination location, bus voltage and timestamps. Export a support bundle before restarting the controller where practical.
TB-031.3
Missing or duplicated 120 ohm end-of-line termination can cause intermittent CRC errors. Verify physical topology against the installation manual before replacing devices.