CS-002.3
Fire-release acceptance
All designated doors must achieve the approved safe state during the witnessed test. A partial result is a failed test.
Commissioning Standard · REVISION 2
Fictional / anonymised ENGGEN 720 demonstration source. SiteAssist reads the stored sections below through controlled read-only tools.
CS-002.3
All designated doors must achieve the approved safe state during the witnessed test. A partial result is a failed test.
CS-002.5
Retain the failed observation, corrective-action approval and final witnessed retest as separate records.
CS-002.7
The field engineer may collect evidence but may not self-approve a life-safety corrective action or commissioning sign-off.