OBS-A-017.1
Observed symptom
A valid card produced Access Granted and the Output 2 indicator changed state, but Door A-12 remained locked.
Observation Sheet · REVISION 1
Fictional / anonymised ENGGEN 720 demonstration source. SiteAssist reads the stored sections below through controlled read-only tools.
OBS-A-017.1
A valid card produced Access Granted and the Output 2 indicator changed state, but Door A-12 remained locked.
OBS-A-017.2
The project wiring schedule identified a fail-secure strike. Output 2 had been configured with Normal logic; changing the 4.2 output logic to Inverted restored normal access operation.
OBS-A-017.3
This observation concerned normal access operation only. It did not test or approve fire-alarm door release.