OBS-A-024.1
Observed symptom
Reader bus 2 accumulated CRC errors after approximately six to eight hours. Readers briefly went offline while the SC-410 remained reachable on IP.
Observation Sheet · REVISION 1
Fictional / anonymised ENGGEN 720 demonstration source. SiteAssist reads the stored sections below through controlled read-only tools.
OBS-A-024.1
Reader bus 2 accumulated CRC errors after approximately six to eight hours. Readers briefly went offline while the SC-410 remained reachable on IP.
OBS-A-024.2
The final reader had no end-of-line termination fitted. Intermediate devices were not terminated.
OBS-A-024.3
A 120 ohm resistor was fitted at the final reader and the bus was placed on an eight-hour soak test.