TR-A-006.1
Reader bus soak
Reader bus 2 completed an eight-hour soak after fitting the 120 ohm end-of-line resistor. CRC counter increase: 0. Result: PASS.
Test Record · REVISION 1
Fictional / anonymised ENGGEN 720 demonstration source. SiteAssist reads the stored sections below through controlled read-only tools.
TR-A-006.1
Reader bus 2 completed an eight-hour soak after fitting the 120 ohm end-of-line resistor. CRC counter increase: 0. Result: PASS.
TR-A-006.2
Door A-12 completed 50 valid-card cycles after the output-logic correction. Normal access release: PASS.
TR-A-006.3
No fire-interface test was included in TR-A-006.